ES

EN

Multiterminal

Heating Cables

View gallery

Products: Parallel Heating Cable (Constant Wattage) | Self-Regulating | Serie | Drain Line | Heating Flanges

< Self-Regulating

ESR-H-BOT

ESR-H-BOT

Download the datasheet PDF

Characteristics

  • Self- Regulating heating cable, bus bar 2x1.25 mm²
  • Application: High
  • Temperature Heating Cable (120º/200ºC)
  • Use: Pipes, tanks, corrosive atmosphere
  • Minimum bending radius 25 mm 10 W/m, 15 W/m, 30 W/m, 45 W/m or 60 W/m at 10ºC
  • 230 V

Applications

Technical Features
Heating wire Copper, nickel-coated
Dimensions cable 10,20 x 4,80 mm
Max. length circuit 10 W/m (205 m), 15 W/m (190 m),
30 W/m (115 m), 45 W/m (85 m), 60W/m (65 m)
Min. installation Tª -40 ºC
Maximum exposure Tª 120ºC (energised) 200ºC (deenergised)
Certificates CE,ATEX,VDE,GOST-R
Tolerance -2.5/+2.5 W
Circuit Length
W/m Starting Tª Maximum Length (m)
    16 A 20 A 32 A
10 W/m -25 175 205 -
10 200 205 -
15 W/m -20 120 152 190
10 165 190 -
30 W/m -20 70 92 115
10 85 114 -
45 W/m -20 50 66 80
10 70 80 -
60 W/m -20 38 52 65
10 50 65 -